Bay of Fundy LNG Developers Downeast LNG and Calais LNG "Spin the Good Spin"

Get the pictures and subscribe at: http://fundytides.blogspot.com

 In a recent MPBN video (see link at fundytides.blogspot.com), Downeast's Rob Wyatt asserted that LNG tankers are accident free. While there are plenty of rumours about accidents, it is true that there are no available reports of major LNG tanker fires. However, they are not "accident free" as Wyatt stated. In fact, the page below from www.ferc.gov shows that there have been numerous ship spills and there are also well-know reports of near disasters from small fires and drifting vessels.

But, we should all be aware that once LNG is revaporized it becomes gas and like "natural gas" and "propane" it is highly combustible. There are literally hundreds of cases of devastating plant fires, pipeline fires, train, and tanker vehicle fires. Gas is NOT a benign commodity. Hundreds of people have been injured or lost their lives in explosions throughout the world some right here in Charlotte and Washington counties.

In its support letter to David Cole, Maine Department of Transportation, Calais LNG clearly indicates, in their stated support for Eastport quest for a rail line, that they intend to ship from their Red Beach location via truck, train, and pipeline. Having finally stated this, CLNG has added a whole new dimension to the risk from any LNG terminal in Passamaquoddy Bay; a risk that was outline to the public two years ago, but may have since become lost in the spin that is currently being dispensed by the LNG promoters.

Once LNG is revaporized it is just another flammable gas and transportation as suggested by Calais LNG does represent a serious risk to the residents of the Quoddy Region, in addition to the risks and disruptions caused by LNG tanker passage and terminal activities. As a result, in the belief that Quoddy citizens need to be informed once again, we will be publishing more reports on gas related fires.

As a starter, please watch this video:



Art

******************

From Ferc Website

 Liquefied Natural Gas Safety

LNG is natural gas that has been refrigerated into a cryogenic liquid so that it can be shipped long distances in carriers. Once an LNG carrier reaches a receiving terminal, the LNG is unloaded and stored in large tanks until it is revaporized and piped into the natural gas distribution network. LNG is a hazardous liquid, because it is cryogenic and, as natural gas, it is combustible.

LNG hazards result from three of its properties: cryogenic temperatures, dispersion characteristics, and flammability characteristics. The extremely cold LNG can directly cause injury or damage. A vapor cloud, formed by an LNG spill, could drift downwind into populated areas. It can ignite if the concentration of natural gas is between five and 15 percent in air and it encounters an ignition source. An LNG fire gives off a tremendous amount of heat.

A large array of laws, regulations, standards, and guidelines are currently in place to prevent and lessen the consequences of LNG releases. These requirements affect LNG facilities' design, construction, operation, and maintenance.

To address terrorist risk, the Ship and Port Facility Security Code was adopted in 2003 by the member countries of the International Maritime Organization (IMO), an agency of the United Nations responsible for maritime matters concerning ship safety. This code requires both ships and ports to conduct vulnerability assessments and to develop security plans. To heighten security of LNG facilities at American seaports, Congress passed the U.S. Maritime Transportation Security Act of 2002, which requires all ports to have federally-approved security plans. Detailed security assessments of LNG facilities and vessels are also required.
The Department of Transportation (DOT), Research and Special Programs Administration, issues and enforces federal safety standards for land-based LNG facilities, although the Federal Energy Regulatory Commission (FERC) can impose more stringent safety requirements than DOT's when warranted. The U.S. Coast Guard (USCG) issues and enforces regulations for waterfront facilities handling LNG.

All of these federal agencies oversee all land and sea-based LNG operations, with some overlapping authorities and some new responsibilities. The recent reactivation of LNG facilities on the East Coast and in the Gulf Coast and permitting of new facilities, have resulted in new methodologies (risk-based decision making) and processes (security workshops, scoping meetings) to assess and communicate safety risk to the public.

Accidents


Explosions and Fires

  • October 1944, Cleveland, Ohio - At the Cleveland peak-shaving plant a tank failed and spilled its contents into the street and storm sewer system. The resulting explosion and fire killed 128 people. The tank was built with a steel alloy that had low-nickel content, which made the alloy brittle when exposed to the extreme cold of LNG.
  • 1964 and 1965 Methane Progress.- While loading LNG in Arzew, Algeria, lightning struck the forward vent riser of the Methane Progress and ignited vapor which was being routinely vented through the ship venting system. A similar event happened early in 1965 while the vessel was at sea shortly after leaving Arzew. In both cases, the flame was quickly extinguished by purging with nitrogen through a connection to the riser.
  • 1969, Portland, Oregon - An explosion occurred in an LNG tank under construction. No LNG had ever been introduced into the tank. The cause of the accident was attributed to the accidental removal of blinds from natural gas pipelines which were connected to the tank. This led to the flow of natural gas into the tank while it was being constructed.
  • January 1972, Montreal East, Quebec, Canada - A back flow of natural gas from the compressor to the nitrogen line occurred during defrosting operations at an LNG liquefaction and peak shaving plant. The valves on the nitrogen were not closed after completing the operation. This caused over-pressurization of the compressor and the natural gas entered the control room (where operators were allowed to smoke) through the nitrogen header. An explosion occurred when an operator tried to light a cigarette.
  • February 1973, Staten Island, New York- While repairing the interior of an empty storage tank, a fire started. The resulting increase in pressure inside the tank was so fast that the concrete dome on the tank lifted and then collapsed down inside the tank killing the 37 construction workers inside.
  • October 1979, Cove Point, Maryland - A natural gas leak caused an explosion killing one plant employee and seriously injuring another and causing about $3 million in damages.
  • April 1983, Bontang, Indonesia - A rupture in an LNG plant occurred as a result of overpressurization of the heat exchanger caused by a closed valve on a blowdown line. The exchanger was designed to operate at 25.5 psig. When the gas pressure reached 500 psig, the exchanger failed and the explosion occurred.
  • August 1987, Nevada Test Site, Mercury, Nevada - An accidental ignition of an LNG vapor cloud occurred at the U.S. Department of Energy Test Site during large-scale tests involving spills of LNG. The cloud was accidentally ignited and damaged and propelled polyurethane pipe insulation outside the fence.
  • June 2004, Trinidad, Tobago - Workers were evacuated after a gas turbine at Atlantic LNG's Train 3 facility exploded.
  • July 2004, Ghislenghien, Belgium - A pipeline carrying natural gas from the Belgian port of Zeebrugge to northern France exploded, resulting in 23 known fatalities. The cause of the incident is still under investigation but it appears that a contractor accidentally damaged the pipe.
  • March 2005, District Heights, Maryland - A Washington Gas company-sponsored study released in July 2005 pointed to subtle molecular differences in the imported liquefied natural gas the utility began using in August 2003 as the cause of a house explosion.

Spills and Leaks

  • Early 1965, Methane Princess Spill - LNG discharging arms were disconnected prematurely before the lines had been completely drained, causing LNG liquid to pass through a partially opened valve and onto a stainless steel drip pan placed underneath the arms. This caused a star-shaped fracture to appear in the deck plating in spite of the application of seawater.
  • May 1965, Jules Verne Spill - LNG liquid spill at Arzew, Algeria, caused by overflowing of a cargo tank that resulted in the fracture of the cover plating of the tank and adjacent deck plating.
  • 1971, La Spezia, Italy - This accident was caused by "rollover" where two layers of LNG with different densities and heat content form. The sudden mixing of these two layers results in the release of large volumes of vapor. In this case, about 2,000 tons of LNG vapor discharged from the tank safety vales and vents over a period of a few hours, damaging the roof of the tank.
  • July 1974, Massachusetts Barge Spill - After a power failure and the automatic closure of the main liquid line valves, 40 gallons of LNG leaked as it was being loaded on a barge. The LNG leaked from a one-inch nitrogen-purge globe valve on the vessel's liquid header. This leak caused several fractures to the deck plates.
  • September 1977, Aquarius Spill - During the filling of a cargo tank at Bontang, LNG overflowed through the vent mast serving that tank. The incident may have been caused by difficulties in the liquid level gauge system. The high-level alarm had been placed in the override mode to eliminate nuisance alarms.
  • March 1978, Das Island, United Arab Emirates - An accident occurred due to the failure of a bottom pipe connection of an LNG tank. The tank had a double wall (a nine-percent nickel steel inner wall and a carbon steel outer wall). Vapor from the outer shell of the tank formed a large heavier-than-air cloud which did not ignite.
  • April 1979, Mostafa Ben Bouliad Spill - While discharging cargo at Cove Point, Maryland, a check valve in the piping system of the vessel failed releasing a small quantity of LNG. This resulted in minor fractures of the deck plating.
  • April 1979, Pollenger Spill - While the vessel was discharging LNG at a terminal in Everett, Massachusetts, LNG leaking from a valve gland apparently fractured one of the tank's cover plating.

Safety Studies